Product features | |
JX3-DIO16 | |
LED membrane | RAL 3020, red |
Degree of protection | IP20 |
Operating temperature | 0 ... +50 °C |
Storage temperature | -40 ... +70 °C |
Air humidity | 10 ... 95 % (non-condensing) |
Mechanical installation | DIN rail to EN 50022 – 35 x 7.5 or EN 50022 – 35 x 15 |
Mounting orientation | Vertical |
Labeling system | Standard terminal labels |
Certifications | CE |
Rated input voltage | DC 24 V (-15 ... +20 %) |
Input current, typical | 3.6 mA, constant |
Total current | 4 A |
Protective circuits | Short-circuit, overload, overtemperature, inductive load |
Pulse stretching range | 0 bis 7.5 ms |
Digital filter range | 0.125 ms through 16 ms |