Product features | |
JX2-IO16 | |
Number of inputs | 8 |
Signal voltage | 0 ... 30 V DC |
Input current | Approx. 8 mA |
Input resistance | 3.0 kΩ |
Signal voltage ON | 16 V minimum |
Signal voltage OFF | 5 V maximum |
Minimum pulse length (inputs 5-8) | 250 µs |
Single-channel counter - max. rate | 2 kHz |
Dual-channel counter - max. rate | 1 kHz |
Number and type of outputs | 8, transistor (pnp) |
Rated voltage | DC 24 V, -15% .. +20% |
Rated output current | 0,5 A |
Protective circuits | Inductive loads, short circuit, overvoltage and overtemperature |
Signal voltage (S) ON | Typically Vsupply -1.5 V |
Electrical isolation | keine |
Connection to basic controller | Via system bus cable (connector: SUB-D, 9 pins) |
Input/output terminals | Screw terminals |
Enclosure | Metal |
Dimensions (WxHxD) | 130 x 103 x 47 mm |
Installation | DIN rail |