JX2-IO16

Number of inputs8
Signal voltage0 ... 30 V DC
Input currentApprox. 8 mA
Input resistance3.0 kΩ
Signal voltage ON16 V minimum
Signal voltage OFF5 V maximum
Minimum pulse length (inputs 5-8)250 µs
 
Single-channel counter - max. rate2 kHz
 
Dual-channel counter - max. rate1 kHz
 
Number and type of outputs8, transistor (pnp)
 
Rated voltageDC 24 V, -15% .. +20%
Rated output current0,5 A
Protective circuitsInductive loads, short circuit, overvoltage and overtemperature
Signal voltage (S) ONTypically Vsupply -1.5 V
Electrical isolationkeine
Connection to basic controllerVia system bus cable (connector: SUB-D, 9 pins)
Input/output terminalsScrew terminals
EnclosureMetal
Dimensions (WxHxD)130 x 103 x 47 mm
InstallationDIN rail