Product features | |
JX2-CNT1 | |
No of counters | 1 single-channel counter, 1 dual-channel counter |
Max. counting rate - single-channel counter | 10 kHz |
Voltage input - single-channel counter | 24 V |
Max. counting rate - dual-channel counter | 500 kHz at 24 V, 1 MHz at 5 V |
Voltage input - dual-channel counter | 24 V with operating point: signal voltage ON: min. 15 V, signal voltage OFF: max. 10 V, 5 V differential mode voltage |
Electrical isolation | None |
Power supply | 20 ... 30 V DC |
Connection to basic controller | Via system bus, male connector SUB-D, 9 pins |
Input terminals | Screw terminals; male connector SUB-D, 15 pins |
Enclosure | Metal |
Dimensions (WxHxD) | 45 x 115 x 69 mm |
Installation | DIN rail |
Heat loss | 0.5 watts |
Heat loss of incremental encoder input | 0.5 watts |
Product features |